Features- Externally visible LED lights up.
Description
The sensing part of the detector consists of two chambers - an open, outer chamber and a semi-sealed reference chamber within. Mounted in the reference chamber is a low activity radioactive foil of Americium 241 which enables current to flow between the inner and outer
chambers when the detector is powered up. As smoke enters the detector, it causes a reduction of the current flow in the outer chamber and hence an increase in voltage measured at the junction between the two chambers. The voltage increase is monitored by the electronic circuitry which triggers the detector into the alarm state at a present threshold. An externally visible red LED lights up when the detector changes to alarm state.
Specification
|
Ordering Code |
PRP/SDI/S6 |
|
|
Supply Voltage |
9 to 33V |
|
|
Average quiescent current at 24V |
28µA |
|
|
Average quiescent current at 9V |
16µA |
|
|
Alarm Current at 24V |
52mA |
|
|
Alarm Current at 9V |
17mA |
|
|
Alarm Indication |
Red LED |
|
|
Normal Operating temperature |
-20 to +60°C |
|
|
(no condensation of icing) |
|
|
|
Max wind continous |
10m/s |
|
|
Remote output (R-) characteristics |
Curent sink to –ve line, limited to 17mA |
|
|
|
Note: when using a remote indicator a current-limiting series |
|
|
|
resistor may be required. |
|
|
|
|