Features- Single Loop Address
- Each Alarm Circuit Fused at 1 amp
- Two Independent Sounder Circuits
- Each Circuit Fully Monitored for Open and Short Circuit Faults
- Auxiliary Monitored Input
- Outputs can be Driven Continuously or Synchronized Pulsed Sounder Drive
- Approved to EFSG for line units
Description
Model PRP/DSC/ESP is a Dual Sounder Controller, which is fully compatible with Hochiki’s ESP analogue addressable protocol. The Dual Circuit Sounder Controller has been designed to provide two, sounder outputs with full fault monitoring. The monitored input can be used for local power supply fault monitoring or as a general purpose input.
The PRP/DSC/ESP utilizes simple DIL switches for reliable addressing and it is available unboxed (as illustrated above) however a separate IP67 rated enclosure is available.
Specification
|
Ordering Code |
PRP/DSC/ESP |
|
|
|
PRP/BOX/ESP (enclosure for above) |
|
|
Operating Voltage |
17-14Vdc |
|
|
External Supply Voltage |
19.2V-30Vdc |
|
|
Low Power Mode |
106µA (typ) |
|
|
Quiescent Current |
290µA (typ) Add: 200ua per Active Sounder Line |
|
|
Current Consumption |
Sounder On: 8mA (per line) |
|
|
(External Supply) |
Sounder Fault: 6mA (per line) |
|
|
Sounder Output Current |
1A/Line Max |
|
|
Sounder Line Capacitance |
0.30µF Max/Line |
|
|
Input EOL Device |
1k., ± 5%, 2W |
|
|
Input Threshold Levels ON = |
470., short cct 50., open cct>100k., EOL = 10k. |
|
|
Weight and (PCB only) |
120g L185xW97xH30mm |
|
|
Dimensions (enclosure only) |
550g L235xW160xH92mm |
|
|
|
|